5 SYSTEM CONFIGURATION
5.4 Structure of CC-Link IE TSN Class B/A Devices (CC-Link IE TSN Protocol Version 1.0 Only) and Ethernet Devices
107
5
Connection cannot be made if the total cyclic data size of all device stations on the CC-Link IE TSN Class A device side
that form a boundary between CC-Link IE TSN Class B and CC-Link IE TSN Class A devices exceeds 2K bytes.
Up to 60 device stations can be connected by using the appropriate master station port in accordance with the CC-Link IE
TSN Class.
No.0: Master station
No.1, No.2: Local station
No.3, No.4, No.5, No.6, No.7, No.8, and No.9: Remote station
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
Set the total cyclic data size within 2K bytes.
No.0: Master station
No.1 to No.7: Remote station
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
Up to 60 devices can be connected in total.
Set the total cyclic data size within 2K bytes.
No.1
Class B
No.2
Class B
No.4
Class B
No.3
Class B
No.8
Class A
No.7
Class A
No.9
Class A
No.0
Class B
No.5
Class A
No.6
Class A
Ò
Ò
Industrial switch
(for CC-Link IE
TSN Class A)
No.5
Class A
No.2
Class B
No.1
Class B
No.4
Class A
No.3
Class A
No.0
Class B
No.6
Class A
No.7
Class A
Ó
Ô
Industrial switch
(for CC-Link IE TSN Class A)