114
5 SYSTEM CONFIGURATION
5.5 Connection Examples
Connection of remote I/O modules and inverters (for star topology)
The following figure shows connection of master/local module + remote I/O modules + inverters (for star topology).
• Device stations can be connected up to the maximum number of connectable stations specified in the CC-
Link IE TSN performance specifications.
• Since the master station has two connection ports (P1 and P2), both the ports can be used to connect
devices. To use only one of them, specific settings are not required.
• A system in which line topology and star topology coexist using an industrial switch (for CC-Link IE TSN
Class B) can be configured. (For the available industrial switches (for CC-Link IE TSN Class B), refer to the
CC-Link Partner Association website (www.cc-link.org).)
• To use an industrial switch (for CC-Link IE TSN Class B), settings such as the IP address and
communication cycle for communicating on CC-Link IE TSN are required.
• Industrial switches (for CC-Link IE TSN Class A) cannot be used. (By using a general-purpose switching
hub, an error related to device station disconnection or time synchronization may occur.)
Connection of local stations
The following figure shows connection of master/local module + local stations.
• Local stations can be connected up to the maximum number of connectable stations specified in the CC-
Link IE TSN performance specifications.
• Depending on the communication mode (unicast mode/multicast mode) of the master station, cyclic
memory map of the local stations changes to the one-to-one range between the master station and a local
station or the range including the communication range of other stations. When a local station shares data
with other stations, use multicast mode.
No.0: FX5-CCLGN-MS (master station)
No.1, No.2, and No.6: Remote I/O module (remote station)
No.3, No.4, and No.5:Inverter (remote station)
No.0: FX5-CCLGN-MS (master station)
No.1, No.2: RJ71GN11-T2 (local station)
No.3, No.4: FX5-CCLGN-MS (local station)
No.0
Class B (1Gbps)
No.1
Class B (1Gbps)
No.2
Class B (1Gbps)
No.3
Class B (1Gbps)
No.4
Class B (1Gbps)
No.5
Class B (1Gbps)
No.6
Class B (1Gbps)
Industrial switch
(for CC-Link IE TSN Class B)
Industrial switch
(for CC-Link IE TSN Class A)
No.0
Class B (1Gbps)
No.1
Class B (1Gbps)
No.2
Class B (1Gbps)
No.3
Class B (1Gbps)
No.4
Class B (1Gbps)