120
5 SYSTEM CONFIGURATION
5.5 Connection Examples
If an industrial switch is used to configure a system (master station: 100Mbps)
The following figure shows connection of master/local module (100Mbps) + inverters. (Only the master station is CC-Link IE
TSN Class B.)
• When all the device stations are CC-Link IE TSN Class A, they can be connected up to the maximum
number of connectable stations specified in the CC-Link IE TSN performance specifications.
• To branch the network with a firmware version of "1.002" or earlier, an industrial switch (for CC-Link IE TSN
Class A) can be used.
• To branch the network with a firmware version of "1.010" or later, an industrial switch (for CC-Link IE TSN
Class B) or an industrial switch (for CC-Link IE TSN Class A) can be used. When using an industrial switch
(for CC-Link IE TSN Class B), set "TSN HUB Setting" to "Use TSN HUB".
• Connection after the industrial switch (for CC-Link IE TSN Class B) or industrial switch (for CC-Link IE TSN
Class A) can be a line topology, star topology, or coexistence of line and star topologies.
• Set "Connection Device Information" of the master station parameters to "Mixture of CC-Link IE TSN Class
B/A or CC-Link IE TSN Class A Only". In addition, because the FX5-CCLGN-MS with a firmware version of
"1.002" or earlier does not support 100Mbps communication, refer to the following.
Page 118 If an industrial switch is used to configure a system (master station: 1Gbps)
No.0: FX5-CCLGN-MS (Master station)
No.1, No.2, No.3, No.4, and No.5: Inverter (Remote station)
No.0
Class B (100Mbps)
No.1
Class A (100Mbps)
No.2
Class A (100Mbps)
No.3
Class A (100Mbps)
No.5
Class A (100Mbps)
No.4
Class A (100Mbps)
Industrial switch
(for CC-Link IE TSN Class A)
or
Industrial switch
(for CC-Link IE TSN Class B)