5 SYSTEM CONFIGURATION
5.5 Connection Examples
121
5
Connection of remote I/O modules and inverters
The following figure shows connection of master/local module + remote I/O modules + inverters.
If the firmware version is "1.002" or earlier, connect in the order of the master station the CC-Link IE TSN
Class B device area the CC-Link IE TSN Class A device area. Use an industrial switch (for CC-Link IE
TSN Class A) on the boundary between the CC-Link IE TSN Class B and CC-Link IE TSN Class A device
areas.
If the firmware version is "1.010" or later, connect in the order of the master station the CC-Link IE TSN
Class B device area the CC-Link IE TSN Class A device area. Use an industrial switch (for CC-Link IE
TSN Class B) or an industrial switch (for CC-Link IE TSN Class A) on the boundary between the CC-Link IE
TSN Class B and CC-Link IE TSN Class A device areas. When using an industrial switch (for CC-Link IE
TSN Class B), set "TSN HUB Setting" to "Use TSN HUB".
If the firmware version is "1.002" or earlier, industrial switches (for CC-Link IE TSN Class B) or industrial
switches (for CC-Link IE TSN Class A) cannot be used on the CC-Link IE TSN Class B side.
If the firmware version is "1.010" or later, industrial switches (for CC-Link IE TSN Class A) cannot be used
on the CC-Link IE TSN Class B side.
If the firmware version is "1.002" or earlier, up to eight CC-Link IE TSN Class B devices can be connected
per port (up to 16 devices for two ports).
If the firmware version is "1.010" or later and any CC-Link IE TSN Class A device that does not support the
CC-Link IE TSN Protocol version 2.0 is included, up to eight CC-Link IE TSN Class B devices can be
connected per port (up to 16 devices for two ports). If all CC-Link IE TSN Class A devices support the CC-
Link IE TSN Protocol version 2.0, nine and more CC-Link IE TSN Class B devices can be connected.
A CC-Link IE TSN Class B device cannot be connected after a CC-Link IE TSN Class A device.
Set "Connection Device Information" of the master station parameters to "Mixture of CC-Link IE TSN Class
B/A or CC-Link IE TSN Class A Only". In "Network Configuration Settings" under "Basic Settings", set
"Communication Period Setting" of the inverters to "Low-Speed". Set "Communication Mode" under
"Application Settings" to "Multicast".
No.0: FX5-CCLGN-MS (master station)
No.1, No.2, No.3, and No.4: Remote I/O module (remote station)
No.5, No.6, and No.7:Inverter (remote station)
CC-Link IE TSN Class B device area
CC-Link IE TSN Class A device area
No.1
Class B (1Gbps)
No.2
Class B (1Gbps)
No.4
Class B (1Gbps)
No.0
Class B (1Gbps)
No.5
Class A (100Mbps)
No.6
Class A (100Mbps)
No.7
Class A (100Mbps)
No.3
Class B (1Gbps)
Class B
Ò Ó
Industrial switch
(for CC-Link IE
TSN Class A)
or
Industrial switch
(for CC-Link IE
TSN Class B)