Item (Detailed display) Description Setting range
Mode Setting The settings for "Module Operation Mode" and "Communication Mode" is
displayed.
For details on the settings, refer to the following.
• Module Operation Mode: Page 139 Module Operation Mode
• Communication Mode: Page 138 Communication Mode
Assignment Method Select a link device assignment method.
• Points/Start: Enter the numbers of points and start numbers of link
devices.
• Start/End: Enter the start and end numbers of link devices.
• Points/Start
• Start/End
(Default: Points/Start)
Cyclic Transmission Time
(Minimum value)
The cyclic transmission time that is calculated by the number of device
stations and the number of link device points is displayed. Use the displayed
value as a guide.
*1*2
The display value can also be checked with 'Cyclic transmission time
(calculation value)' (SW0073). (Page 275 List of Link Special Register
(SW))
The displayed value differs depending on "TSN HUB Setting" of "Connection
Device Information" under "Basic Settings" even when the number of device
stations and link device points are the same. For details, refer to the
following.
Page 286 Communication cycle intervals
The displayed value can be used for "Cyclic Transmission Time" in
"Communication Period Setting" under "Basic Settings" of the module
parameter.
If the cyclic transmission is not performed while the displayed value is set,
set a value obtained by the following formula: Value displayed in Cyclic
Transmission Time (Min.) + Greatest value among the two values shown
below.
• 10% of the minimum value of the calculated cyclic transmission time
• When the communication speed of the master station is set to 1Gbps:
Number of device stations 2s
• When the communication speed of the master station is set to 100Mbps:
Number of device stations 20s
Communication Period
Interval (Minimum value)
The communication cycle intervals that are calculated by the number of
device stations and the number of link device points are displayed. Use the
displayed value as a guide.
*1*2
The display value can also be checked with 'Communication cycle interval
(calculation value)' (SW0072). (Page 275 List of Link Special Register
(SW))
The displayed value differs depending on "TSN HUB Setting" of "Connection
Device Information" under "Basic Settings" even when the number of device
stations and link device points are the same. For details, refer to the
following.
Page 286 Communication cycle intervals
No. The total number of device stations set in the "CC-Link IE TSN
Configuration" window is displayed.
Model Name The module model name is displayed.
To set a module where the profile is not registered, select it from the
"General CC-Link IE TSN Module" list or register the profile before setting
the model name.
For how to register a profile, refer to the following.
GX Works3 Operating Manual
STA# Enter the station number of each device station connected to the network.
Station numbers do not need to be set consecutively, but must be unique.
• Master station: Fixed to "0"
• Device station: 1 to 120
(Default: Serial number of added stations)
Station Type Set the station types. Select the station types same as those of the modules
connected to the network.
•Master Station
• Local Station
• Remote Station
(Default: Varies depending on the set module)
Motion Control Station Set whether to use the station as a target station for motion control. • Motion control target
• Not motion control target
(Default: Not motion control target)