7 PARAMETER SETTINGS
7.5 "CC-Link IE TSN Configuration" Window
RX Setting
*3
Assign RX/RY points in increments of 16. ( Page 27 Communications
using RX, RY, RWr, and RWw)
Modules with settings provided by profile are automatically set from selected
models. (Excluding modules with a number of points that is not fixed)
Number of points: 16 to 8192
Start: 0H to 1FF0H
End: FH to 1FFFH
(Default: Varies depending on the set module)
RY Setting
*3
RWw Setting
*3
Assign RWw/RWr points in increments of 4. ( Page 27 Communications
using RX, RY, RWr, and RWw)
Modules with settings provided by profile are automatically set from selected
models. (Excluding modules with a number of points that is not fixed)
Number of points: 4 to 4096
Start: 0H to FFCH
End: 3H to FFFH
(Default: Varies depending on the set module)
RWr Setting
*3
Parameter Automatic Setting Set whether to set the parameters of each device station automatically.
This cannot be set for extension modules. However, the parameter
automatic setting of extension modules is interlocked with the settings of the
connected main module.
Check: Distribute parameters
Do Not check: Do not distribute parameters
(Default: Do Not check)
PDO Mapping Setting Set the PDO mapping to the station that supports CANopen
communications. ( Page 149 PDO mapping setting)
IP Address Set the IP address of a station that performs cyclic transmission. 0.0.0.1 to 223.255.255.254
(Default: The first to third octets have the
same values as the master station, the fourth
octet has a serial number from 1 to 254)
Subnet Mask Set a subnet mask to identify a network address.
Set the same value for the master station and device station. Even if a
device station has a different subnet mask from the master station, it does
not result in an input error.
If 255.255.255.255 is set, leave it empty.
0.0.0.1 to 255.255.255.255
•Empty
(Default: The same value if there is a master
station)
Default Gateway Set the default gateway address to connect to the external network. 0.0.0.1 to 223.255.255.254
•Empty
(Default: empty)
Reserved/Error Invalid Station Set the device station as a reserved station or error invalid station.
No Setting: The device station is connected to the network.
Reserved Station: The device station is reserved in the parameters for
future expansion. By using a reserved station, link device assignment will
not change even if the device station is added (reservation is canceled).
Therefore, modification of the program is not required. Physical
connection of the device station on the network is not required.
Error Invalid Station: Even if a device station is disconnected during data
link, the master station will not detect the device station as a faulty station.
No Setting
Reserved Station
Error Invalid Station
(Default: No setting, master station is fixed as
empty)
Communication Period Setting When multiple communication cycles are set, set the cycle of each device
station. ( Page 39 Communication cycle coexistence)
•Basic Period
Normal-Speed
Low-Speed
(Default: Basic cycle, master station is fixed
as empty)
Station Information Alias
Enter the name of a device if required.
The name entered is displayed in "Network Status" of the "CC-Link IE TSN/
CC-Link IE Field Diagnostics" window.
For the extension module of the remote station, the name is not displayed in
the "CC-Link IE TSN/CC-Link IE Field Diagnostics" window, even if entered.
Up to 32 one-byte characters (one-byte or
two-byte)
(Default: empty)
Comment
Information entered in "Comment1" on the "Properties" window displayed by
right-clicking the module in the list of stations or the network map is
displayed.
Up to 32 one-byte characters (one-byte or
two-byte)
(Default: empty)
Station-specific mode setting
Set the station-specific mode of the device station. (Only when the device
station supports the station-specific mode)
The setting varies depending on the set
module.
CC-Link IE TSN Class Set the CC-Link IE TSN Class of the device for each device station.
*3
CC-Link IE TSN Class B
CC-Link IE TSN Class A
(Default: Varies depending on the device)
Item (Detailed display) Description Setting range

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-F Series

Related product manuals