10 TROUBLESHOOTING
10.5 List of Error Codes
237
10
D273H The request data size of transient transmission is
incorrect.
Correct the request command at the transient request source, and
retry the operation.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
D275H Other dedicated instructions are in execution, and
the executed instruction cannot be processed.
Other dedicated instructions are in execution. Execute again after
a while.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
D27AH The own station number set in the UINI instruction
is incorrect.
Set the station number of the own station in the control data to a
value from 1 to 120, and retry the operation.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
D27BH The IP address set in the UINI instruction is
incorrect.
Execute again after correcting the IP address in the control data.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
D27CH System error Please consult your local Mitsubishi representative.
D27FH System error Please consult your local Mitsubishi representative.
D2C0H
to
D2D1H
System error Please consult your local Mitsubishi representative.
D2D2H The IP address/port number of the target station
is incorrect.
Execute again after correcting the port number of the target station
in the setting data.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
D2D3H Send processing of the transient transmission has
failed.
Check the network status using the CC-Link IE TSN/CC-Link IE
Field diagnostics of the engineering tool, and take action.
When the own station, target station, or relay station detected an
error, identify the cause of the error and take action.
Correct the target IP address of transient data, and retry the
operation.
D602H Parameter error Write the network parameter to the CPU module again.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
D605H Parameter error Write the network parameter to the CPU module again.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
D60BH
to
D610H
System error Please consult your local Mitsubishi representative.
D611H Parameter error (each station device range
assignment error (RWw))
Write the network parameter to the CPU module again.
Execute again after correcting the size of the device station link
device in the setting data.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
D612H Parameter error (each station device range
assignment error (RWw))
Write the network parameter to the CPU module again.
Execute again after correcting the offset of the device station link
device in the setting data.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
D613H Parameter error (each station device range
assignment error (RWr))
Write the network parameter to the CPU module again.
Execute again after correcting the size of the device station link
device in the setting data.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
D614H Parameter error (each station device range
assignment error (RWr))
Write the network parameter to the CPU module again.
Execute again after correcting the offset of the device station link
device in the setting data.
If the error occurs again even after taking the above, please
consult your local Mitsubishi representative.
Error
code
Error definition and causes Action Detailed
information 1
Detailed
information 2