192
6 BASIC INSTRUCTIONS
6.1 Comparison Operation Instructions
Operation error
In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
*2 There are CPU modules that will not result in an operation error if -0 is specified. For details, refer to Page 87 Using single/double-
precision real number data.
Program example
The following program compares 32-bit floating decimal point real number data at D0 and D1 to 32-bit floating decimal point
real number data at D3 and D4.
The following program compares the floating decimal point real number 1.23 to the 32-bit floating decimal point real number
data at D3 and D4.
The following program compares 32-bit floating decimal point real number data at D0 and D1 to 32-bit floating decimal point
real number data at D3 and D4.
The following program compares the 32-bit floating decimal point data at D0 and D1 to the floating decimal point real
number 1.23.
Error
code
Error details Q00J/
Q00/
Q01
QnH QnPH QnPRH QnU LCPU
4100 The specified device value is -0.
*2

*2

4140 The specified device value is not within the following range:
0, 2
-126
| Specified device value | < 2
128
The specified device value is -0, unnormalized number, nonnumeric, and .

*2
[Ladder Mode] [List Mode]
[Ladder Mode] [List Mode]
[Ladder Mode] [List Mode]
[Ladder Mode] [List Mode]
Step
Instruction
Device
Step
Instruction
Device
Step
Instruction
Device
Step
Instruction
Device