Set the SV. <50°C>
Set the input filter
constant (α). <70%>
Set the derivative gain (K
D). <0%>
Set the ULV. <On time: 2 seconds>
Set the LLV. <On time: 0 seconds>
Start the auto tuning setting.
Auto tuning action status flag
Set the sampling time (T
S) for auto
tuning. <3 seconds>
Turn on the auto tuning execution
bit in action setting (ACT)
parameter.
Set the auto tuning output cycle.
<On time: 1.8 seconds>
Set the sampling time (T
S) for
normal PID action. <500ms>
Input the PV to the I/O data area
from the A/D converter module.
Initialize PID output.
Execute the PID instruction.
PID action being performed
Check the auto tuning action.
End the auto tuning processing.
Switch to the normal PID action.
Heater output
Write the manipulated value
to the D/A converter module.
Error