948
APPENDICES
Appendix 1 Operation Processing Time
Processing time of instructions other than subset instruction
The following table shows the processing time of instructions other than subset instructions.
The processing time shown in "Table of the processing time of instructions other than subset instructions"
applies when the device used in an instruction does not meet the device condition for subset processing.
(For device condition that does not trigger subset processing, refer to Page 108 Subset processing.) For
instructions not shown in the following table, refer to Page 921 Subset instruction processing time.
When using the file resister (R, ZR), extended data register (D), extended link register (W), module access
device (Un\G, U3En\G0 to G4095) or link direct device (Jn\), add the processing time shown in Page
1022 Table of the time to be added when file register, extended data register, extended link register, module
access device, and link direct device are used to that of each instruction.
Since the processing time of an instruction varies depending on that of the cash function, both the minimum
and maximum values are described in the table.
Table of the processing time of instructions other than subset instructions
When using Q00UJCPU, Q00UCPU, Q01UCPU and Q02UCPU
Category Instruction Condition (device) Processing time (s)
Q00UJCPU Q00UCPU Q01UCPU Q02UCPU
Min. Max. Min. Max. Min. Max. Min. Max.
Sequence
instruction
ANB
ORB
MPS
MRD
MPP
0.120 0.080 0.060 0.040
INV When not executed 0.120 0.080 0.060 0.040
When executed
MEP
MEF
When not executed 0.120 0.080 0.060 0.040
When executed
EGP
EGF
When not executed 0.120 0.080 0.060 0.040
When executed
PLS 1.800 1.900 1.800 1.900 1.800 1.900 1.300 1.600
PLF 1.800 1.900 1.800 1.900 1.800 1.900 1.600 1.700
FF When not executed 0.240 0.160 0.120 0.080
When executed 1.700 1.800 1.700 1.800 1.700 1.800 1.200 1.500
DELTA When not executed 0.240 0.160 0.120 0.080
When executed 4.000 14.700 4.000 14.700 4.000 14.700 2.800 3.600
SFT When not executed 0.240 0.160 0.120 0.800
When executed 1.800 12.600 1.800 12.600 1.800 12.600 1.600 6.600
MC 0.240 0.160 0.120 0.080
MCR 0.120 0.080 0.060 0.040
FEND
END
Error check performed 250.000 250.000 250.000 250.000 250.000 250.000 175.000 252.000
No error check performed 250.000 250.000 250.000 250.000 250.000 250.000 175.000 221.000
STOP 
NOP
NOPLF
PAGE
0.120 0.080 0.060 0.040