172
Frequency setting by analog input (terminal 1, 2, 4)
4.16.4 Bias and gain of frequency setting voltage (current)
(Pr. 125, Pr. 126, Pr. 241, C2(Pr. 902) to C7(Pr. 905))
You can set the magnitude (slope) of the output frequency as desired in relation to the frequency setting signal (0
to 5V, 0 to 10V or 4 to 20mADC).
Set Pr. 73 and Pr. 267 to switch between 0 to 5VDC, 0 to 10VDC and 4 to 20mADC. (Refer to page 166)
Parameter
Number
Name Initial Value
Setting
Range
Description
125
Terminal 2 frequency setting gain
frequency
50Hz 0 to 400Hz
Set the frequency of terminal 2 input gain
(maximum).
126
Terminal 4 frequency setting gain
frequency
50Hz 0 to 400Hz
Set the frequency of terminal 4 input gain
(maximum).
241
*1, 3
Analog input display unit
switchover
0
0 Displayed in %
Select the unit of
analog input display.
1 Displayed in V/mA
C2(902)
*1, 2
Terminal 2 frequency setting bias
frequency
0Hz 0 to 400Hz
Set the frequency on the bias side of
terminal 2 input.
C3(902)
*1, 2
Terminal 2 frequency setting bias 0% 0 to 300%
Set the converted % of the bias side
voltage (current) of terminal 2 input.
C4(903)
*1, 2 Terminal 2 frequency setting gain 100% 0 to 300%
Set the converted % of the gain side
voltage (current) of terminal 2 input.
C5(904)
*1, 2
Terminal 4 frequency setting bias
frequency
0Hz 0 to 400Hz
Set the frequency on the bias side of
terminal 4 input.
C6(904)
*1, 2 Terminal 4 frequency setting bias 20% 0 to 300%
Set the converted % of the bias side
current (voltage) of terminal 4 input.
C7(905)
*1, 2 Terminal 4 frequency setting gain 100% 0 to 300%
Set the converted % of the gain side
current (voltage) of terminal 4 input.
*1 The parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 185.)
*2 The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
*3 The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter
write selection.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi F700 Series and is the answer not in the manual?

Mitsubishi F700 Series Specifications

General IconGeneral
Humidity95% RH or less (non-condensing)
Control MethodV/F control
Protection FeaturesOvercurrent, overvoltage, undervoltage, overheat, short circuit
Communication OptionsRS-485
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
AltitudeUp to 1000m above sea level
Overload Capacity150% for 60 seconds
Cooling MethodForced air cooling
Power Range0.75 to 630 kW (1 to 845 hp)
Output Voltage3-phase 200 to 240 VAC, 380 to 500 VAC (matching input voltage)