319
Parameter clear
4
PARAMETERS
4.25 Parameter clear
POINT
· Set "1" in Pr. CL parameter clear to initialize parameters. (Parameters are not cleared when "1" is set in Pr. 77
Parameter write selection. In addition, calibration parameters are not cleared.)
Setting Description
0 Not executed.
1
Returns all parameters to the initial values except for calibration parameters, terminal function selection
parameters, etc.
Refer to the list of parameters on page 384 for availability of parameter clear.
and are displayed alternately ... Why?
The inverter is not in the PU operation mode.
1. Press .
is lit and the monitor (4 digit LED) displays "0" (Pr. 79 = "0" (initial value)).
2. Carry out operation from step 6 again.
1.
Screen at powering ON
The monitor display appears.
Display
Operation
3.
Press to choose the parameter
setting mode.
Flicker ··· Parameter setting complete!!
7.
Press to set.
5.
Press to read the present set value.
" "(initial value) appears.
PU indication is lit.
2.
Press to choose the PU operation
mode.
· Turn to read another parameter.
· Press twice to show the next parameter.
· Press to show the setting again.
4.
Turn until " " (parameter clear)
appears.
6.
Turn to change it to
the setting value " ".
The parameter
number read
previously appears.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi F700 Series and is the answer not in the manual?

Mitsubishi F700 Series Specifications

General IconGeneral
Humidity95% RH or less (non-condensing)
Control MethodV/F control
Protection FeaturesOvercurrent, overvoltage, undervoltage, overheat, short circuit
Communication OptionsRS-485
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
AltitudeUp to 1000m above sea level
Overload Capacity150% for 60 seconds
Cooling MethodForced air cooling
Power Range0.75 to 630 kW (1 to 845 hp)
Output Voltage3-phase 200 to 240 VAC, 380 to 500 VAC (matching input voltage)