29
Control circuit specifications
2
WIRING
2.3.5 Mounting the operation panel (FR-DU07) on the enclosure surface
Having an operation panel on the enclosure surface is convenient.
With a connection cable, you can mount the
operation panel (FR-DU07) or the parameter unit (FR-PU07) to the enclosure surface, and connect it to the inverter.
Use the option FR-CB2

, or the connector and cable available on the market.
(For mounting the operation panel (FR-DU07), the optional connector (FR-ADP) is required.)
Securely insert one end of connection cable until the stoppers are fixed.
Refer to page 209 for RS-485 communication.
REMARKS
· Refer to the following when fabricating the cable on the user side. Keep the total cable length within 20m.
Commercially available product examples (as of January 2010)
STF FWD PU
Parameter unit connection cable
(FR-CB2)(option)
Operation panel(FR-DU07)
Parameter unit (FR-PU07)
(option)
Operation panel connection connector
(FR-ADP)(option)
* Do not use pins No. 2, 8 of the communication cable.
Product Type Maker
Communication cable
SGLPEV-T (Cat5e/300m)
24AWG × 4P*
Mitsubishi Cable Industries, Ltd.
RJ-45 connector 5-554720-3 Tyco Electronics Corporation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi F700 Series and is the answer not in the manual?

Mitsubishi F700 Series Specifications

General IconGeneral
Humidity95% RH or less (non-condensing)
Control MethodV/F control
Protection FeaturesOvercurrent, overvoltage, undervoltage, overheat, short circuit
Communication OptionsRS-485
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
AltitudeUp to 1000m above sea level
Overload Capacity150% for 60 seconds
Cooling MethodForced air cooling
Power Range0.75 to 630 kW (1 to 845 hp)
Output Voltage3-phase 200 to 240 VAC, 380 to 500 VAC (matching input voltage)

Related product manuals