190
Selection of operation mode and
operation location
4.18 Selection of operation mode and operation location
4.18.1 Operation mode selection (Pr. 79)
The above parameters can be changed during a stop in any operation mode.
* The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog
input (AU) > digital input from the operation panel".
Purpose Parameter that must be set Refer to page
Operation mode selection Operation mode selection Pr. 79 190
Started in network operation mode Operation mode at power ON Pr. 79, Pr. 340 198
Selection of operation location
Selection of start command source, speed
command source and operation location
during communication operation
Pr. 338, Pr. 339,
Pr. 550, Pr. 551
199
Used to select the operation mode of the inverter.
Mode can be changed as desired between operation using external command signals (external operation), operation
from the PU (FR-DU07/FR-PU04/FR-PU07), combined operation of PU operation and external operation (external/PU
combined operation, and network operation (when RS-485 terminals or a communication option is used).
Parameter
Number
Name
Initial
Value
Setting
Range
79 Operation mode selection
0 0 to 4, 6, 7
POINT
• Use the simple setting mode to set Pr. 79 in simple steps. (Refer to page 54)
Pr.79
Setting
Description
LED Indication
: OFF : ON
Refer
to
0
Use external/PU switchover mode (press to switch between the PU and External
operation mode.
At power ON, the inverter is in the External operation mode.
PU operation mode
External operation mode
NET operation mode
193
1
Operation mode Frequency command Start command
PU operation mode
193
PU operation mode (fixed)
Setting by the operation
panel (FR-DU07) and PU
(FR-PU04/FR-PU07)
Input by and on
PU (FR-DU07/FR-PU04/
FR-PU07)
2
External operation mode (fixed)
The operation can be
performed by switching
between the External and NET
operation modes.
External signal input (from
terminal 2, 4, and 1, JOG,
multi-speed selection, etc.)
External signal input (from
terminal STF and STR)
External operation mode
NET operation mode
193
3
External/PU combined
operation mode 1
PU (FR-DU07/FR-PU04/FR-
PU07) setting or external
signal input (multi-speed
setting, across terminals 4
and 5 (valid when AU signal
turns ON)). *
External signal input
(terminal STF, STR)
194
4
External/PU combined
operation mode 2
External signal input
(Terminal 2, 4, 1, JOG,
multi-speed selection, etc.)
Input by and on
PU (FR-DU07/FR-PU04/
FR-PU07)
194
6
Switchover mode
Switch among PU operation, External operating, and NET operation while keeping the
same operating status.
PU operation mode
External operation mode
NET operation mode
195
7
External operation mode (PU operation interlock)
X12 signal ON: Operation mode can be switched to the PU operation mode.
(output stop during external operation)
X12 signal OFF: Operation mode cannot be switched to the PU operation mode.
195
REMARKS
If switching of the operation mode is invalid even though Pr. 79 is set, refer to page 347.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi F700 Series and is the answer not in the manual?

Mitsubishi F700 Series Specifications

General IconGeneral
Humidity95% RH or less (non-condensing)
Control MethodV/F control
Protection FeaturesOvercurrent, overvoltage, undervoltage, overheat, short circuit
Communication OptionsRS-485
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +65°C
AltitudeUp to 1000m above sea level
Overload Capacity150% for 60 seconds
Cooling MethodForced air cooling
Power Range0.75 to 630 kW (1 to 845 hp)
Output Voltage3-phase 200 to 240 VAC, 380 to 500 VAC (matching input voltage)

Related product manuals