Appendix
10/05 AWB8230-1541GB
204
Parameter protection
To protect the parameters saved to the keypad, you can disable
the READ command. To do this, press the MNT, ú and STOP keys
at the same time for about two seconds.
With arrow keys í, Í and Ú you can select and toggle the read
function (READ LOCK = ON).
To enable this function, press ENTER. To exit the configuration
menu, press RMT.
Copy function
X Press the COPY key.
All parameters saved in the keypad are transferred to the
connected device.
Fault messages, the content of the fault register and the
configuration for the software parameter protection are not
transferred.
Impermissible attempts to copy data are automatically terminated
and error message R-ERROR INV.TYPE is displayed. You must
acknowledge the error message with the ENTER key.
h
All parameter changes are written directly to the
connected device. For the Copy function, you must first
load the changes in the keypad with the READ function.
h
The copy function can be used only when the drive is at
standstill (in STOP state). During operation, in error
condition, during resetting and with software protection
enabled, this function is not available.
h
The keypad allows the transfer of parameters only
between frequency inverters and speed control units of
the same device series with the same rating.
h
When you copy data between devices of the same series
but with different ratings, you must adapt the ratings data
(current limitation, overload protection, etc.) for each new
device.
h
Caution!
Do not copy parameters between 230 V and 400 V
frequency inverters of the same series (for example
DF51-322… and DF51-340…).
h
Caution!
Never copy data between devices with different operating
systems (for example to Japanese or American versions).
The DF5, DF51, DF6, DV5, DV51, DV6 and RA-SP devices
described here have a European operating system.
CONFIGURATION
READ LOCK
OFF
WRITER REMT -> INV WRITER REMT->->INV
R-ERROR INV.TYPE
h
AWB8240-1416…