10/05 AWB8230-1541GB
Electrical connection
47
Terminal H outputs +10 V (max. 10 mA) to provide the setpoint
voltage for supplying an external potentiometer. Reference point
is terminal L.
Table 12: Actuating the analog inputs
Figure 46: Control signal terminal strip (part 2)
11AMLOI
R
B
R
i
OH12CM2
+10 V DC
F 10 mA
0...10 V DC
F 1 mA
F +27 V DC
F 50 mA
F +27 V DC
F 50 mA
F 100 mA
0...10 V DC
R
i
= 10 k O
0 V
4...20 mA
R
B
= 250 O
–
+
h
All analog inputs and outputs use terminal L as reference
potential and are therefore also connected to the
reference potential of digital inputs 1 to 5.
Circuit example Description
• Frequency reference input (default = 0 to 50 Hz) through
an external potentiometer (recommended fixed resistance
1to5kO).
• Standard circuit
• Frequency reference input (default = 0 to 50 Hz) through
an external 4 to 20 mA current signal.
• Standard circuit
MAX
0
+
–
O
0 V
+10 V
L
H
R
i
= 10 kO
R1
4...20 mA
OI
0 V
L
R
B
250 O
h
At the default setting, the input signals at terminals O
(0 to 10 V) and OI (4 to 20 mA) are added to the resulting
frequency reference input. You can select the reference
source with parameter PNU A005 (AT selection) and
activate it through a control signal terminal
(PNU C00x = 16).