ioLogik E2210 User’s Manual Click&Go Logic
5-7
Active Message
Select Active Message for active I/O messaging over TCP or UDP. Click the memo icon to configure the
message and parameters. Note that TCP and UDP cannot be used at the same time within a ruleset – all
rules must use the same protocol.
After clicking the memo icon, you may enter your desired message in the Message Content window. If
necessary Dynamic fields such as time, date, IP address, and I/O status may be inserted in your message
by clicking on the Keyword Lookup button. Up to 10 IP destinations for the message can be specified in
the Message Receiver list. The default Message Port is 9000, and this can be modified as necessary to
work with your firewall.
By default, messages are sent in ASCII, although ioAdmin can display the message in HEX in Message
Monitor.
Messages may also be entered in HEX by selecting the “Send as HEX” checkbox. When sending a
message in HEX, each HEX value must be entered using the decimal equivalent, delimited by commas.
Note that certain numbers are control characters that will not show up in the Message Monitor. Please
refer to the following example.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E2210 and is the answer not in the manual?

Moxa Technologies ioLogik E2210 Specifications

General IconGeneral
BrandMoxa Technologies
ModelioLogik E2210
CategoryI/O Systems
LanguageEnglish

Related product manuals