ioLogik E2210 User’s Manual Click&Go Logic
5-13
Click&Go Logic and Peer-to-Peer I/O Demo
Scenario 1
In this scenario, we have two switches, one attached to DI(0) and one attached to DO(0). Very simply, we
want DO(0) to automatically mirror DI(0)’s setting. Once the ruleset is downloaded onto the ioLogik
E2210 and activated, the server handles all processing locally and there is no usage of network or host
resources.
Rule 0: IF DI(0)=ON, THEN DO(0)=ON
Rule 1: IF DI(0)=OFF, THEN DO(0)=OFF.
1. In ioAdmin, make sure that you have logged in on the Server Settings tab. Go to the Click&Go
Logic tab.
2. Double click on #0 in the Rules List. The rule configuration window will appear.
3. Make sure that Enable in the upper left hand corner is checked.
4. Select Enable Logic.
5. Select DI(0) as your condition in the first IF field, and set its value to ON.
6. Select DO(0) as your action in the first THEN field, and set its value ON.
7. Click on OK.
8. Double click on #1 in the Rules List.
9. Make sure that Enable in the upper left hand corner is checked.
10. Select Enable Logic.
11. Select DI(0) as your condition in the first IF field, and set its value to OFF.
12. Select DO(0) as your action in the first THEN field, and set its value OFF.
13. Click on OK.
14. Click on
Download on the Ruleset Management Bar.
15. Select Ye s when asked to restart and wait until the server has restarted and is back on-line.
16. Log in on the Server Settings tab, then go to the Click&Go Logic tab.
17. Click on Run on the Ruleset Management Bar. The RDY LED will be flashing green, showing
that the server is now operating as an Active Ethernet I/O server, using the ruleset that was just
defined.
Scenario 2
In this scenario, we have a switch attached to DI(0). We want the server to send a TCP message that
indicates the exact time that the switch is turned on.
Rule 0: IF DI(0)=ON, THEN Message
1. In ioAdmin, make sure that you have logged in on the Server Settings tab. Go to the Click&Go
Logic tab.
2. Double click on #0 in the Rules List. The rule configuration window will appear.
3. Make sure that Enable in the upper left hand corner is checked.
4. Select Enable Logic.
5. Select DI(0) as your condition in the first IF field, and set its value to ON.
6. Select Active Message as your action in the first THEN field.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E2210 and is the answer not in the manual?

Moxa Technologies ioLogik E2210 Specifications

General IconGeneral
BrandMoxa Technologies
ModelioLogik E2210
CategoryI/O Systems
LanguageEnglish

Related product manuals