13 Technical data
Maschinenfabrik Reinhausen GmbH 2022 1918595028/00 EN TAPCON
®
250
13.2.8 Digital outputs DO 8
DO8
Outputs (plug-based electrical isola-
tion)
8 relays
4 groups per module
Switching voltage DC: 24V, 48V, 60V, 110V
AC: 110V
Contact load capacity Min.: 5VDC, 10mA
Max. DC: See diagram
Max. AC: 150V; 3A (8active outputs)
or 5A (4active outputs)
Table76: DO8 assembly technical data
10
20
30
40
50
100
V
300
0.1 0.2 0.5 1 2 5 10 20A
U
I
Ohmic load
Figure88: Contact load capacity of digital outputs with resistive load
CAUTION
Electric shock!
The outputs of the DO assembly have plug-based electrical isolation. A mix-
ture of voltage ranges (e.g. extra low voltage and low voltage) or various
phases within a plug can lower the protection against electric shock.
► Use the same voltage ranges within a plug.
► Use the same phase within a plug.