3-30
3-7 Parameter List
3
Operation
Non-stop function at momentary power interruption
b050
Selection of non-
stop function at
momentary power
interruption
00: Disabled
01: Enabled (Stop)
02: Enabled (Restart)
00 No 4-33
b051
Starting voltage of
non-stop function
at momentary
power interruption
0.0 to 1000. 0.0 No V 4-33
b052
Stop deceleration
level of non-stop
function at
momentary power
interruption
0.0 to 1000. 0.0 No V 4-33
b053
Deceleration time
of non-stop
function at
momentary power
interruption
0.01 to 99.99
100.0 to 999.9
1000 to 3000
1.0 No s 4-33
b054
Deceleration
starting width of
non-stop function
at momentary
power interruption
0.0 to 10.0 0.0 No Hz 4-33
Others
b055
Overvoltage
protection
proportional gain
during
deceleration
0.2 to 5.0 0.2 Yes ⎯ 4-35
b056
Overvoltage
protection integral
time during
deceleration
0.0 to 150.0 0.2 Yes s 4-35
b080 AM adjustment
0. to 255.
(Shared with C086 for AM offset adjustment)
100. Yes ⎯
4-35
4-75
b082 Starting frequency 0.5 to 9.9 1.5 No Hz 4-36
b083 Carrier frequency 2.0 to 12.0 3.0 No kHz
4-36
4-76
Initialization
b084
Initialization
selection
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes data
00 No ⎯ 4-38
b085
Initialization
parameter
selection
00
* Do not change.
00 No ⎯ 4-38
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Changes
during
operation
Unit Page
* 2nd control is displayed when SET (08) is allocated to one of from C001 to C005.