322
PLC Setup Section 7-1
Pulse Output 0 Origin Detection Method
Pulse Output 0 Origin Search Direction Setting
Pulse Output 0 Origin Search/Return Initial Speed
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 0 Origin Search High Speed
Note When the CX-Programmer is being used to make the setting, the setting is
input in decimal.
Pulse Output 0 Origin Search Proximity Speed
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+257 08 to 11 0 hex: Method 0
(Origin detection
method 0)
1 hex: Method 1
(Origin detection
method 1)
2 hex: Method 2
(Origin detection
method 2)
0 hex Specifies the origin detection method
for pulse output 0.
--- When operation
starts
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+257 12 to 15 0 hex: CW direc-
tion
1 hex: CCW
direction
0 hex Specifies the origin search direction
for pulse output 0.
--- When operation
starts
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+258 00 to 15 00000000 to
000186A0 hex
(See note.)
00000000
hex
Specifies the starting speed (0 to
100,000 pps) for the pulse output 0
origin search and origin return opera-
tions.
--- When operation
starts
+259 00 to 15
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+260 00 to 15 00000001 to
000186A0 hex
(See note.)
00000000
hex
Specifies the high speed setting (1 to
100,000 pps) for pulse output 0 origin
search operation.
--- When operation
starts
+261 00 to 15
Programming
Console
address
Settings Default Function Related
Auxiliary
Area flags/
bits
Time when
setting is read
by CPU Unit
Word Bits
+262 00 to 15 00000001 to
000186A0 hex
(See note.)
00000000
hex
Specifies the proximity speed setting
(1 to 100,000 pps) for pulse output 0
origin search operation.
When operation
starts
+263 00 to 15

Table of Contents