5-2
This section explains the basic settings required to operate and stop the
Inverter.
The settings of parameters described here will be sufficient for simple
Inverter operations.
First,makethesebasicsettings,thenskiptotheexplanationsofthosespe-
cialfunctions,evenwhenyourapplicationrequiresspecial functions,such
as energy-saving control, PID control, stall prevention, carrier frequency
setting, overtorque detection, torque compensation, slip compensation.
Refer to Chapter 6 Advanced Operation.
5-1 Initial Settings
·The following initial settings are required.
Parameter Write-prohibitSelection/ParameterInitialization (n001): Set n001 to 4so
that n001 through n179 can be set or displayed.
Control Mode Selection (n002): Set to V/f or vector control mode according to the
application.
5-1-1 Setting the Parameter Write-prohibit
Selection/Parameter Initialization (n001)
·Set n001 to 4 so that n001 through n179 can be set or displayed.
n001 Parameter Write-prohibit
Selection/Parameter Initialization
Register 0101
Hex
Changes during
operation
No
Setting
range
0 to 9 Unit of
setting
1 Default setting 1
Note This parameter makes it possible to write-prohibit parameters, change the
parameter set or displayed range, or initialize all parameters to default values.
Basic Operation Chapter 5