EasyManua.ls Logo

Omron SYSDRIVE 3G3MV

Omron SYSDRIVE 3G3MV
348 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-4
4-1 Procedure for Test Run
1. Installation and Mounting
InstalltheInverteraccordingtotheinstallationconditions.Refertopage2-2.Ensure
that the installation conditions are met.
2. Wiring and Connection
Connect to the power supply and peripheral devices. Refer to page 2-11. Select
peripheral devices which meet the specifications and wire correctly.
3. Power Connection
Carry out the following pre-connection checks before turning ON the power supply.
S Alwaysensurethatapowersupplytothecorrectvoltageisusedandthatthepower
input terminals (R/L1, S/L2, and T/L3) are wired correctly.
3G3MV-A2j: 3-phase 200 to 230 VAC
3G3MV-ABj: Single-phase 200 to 240 VAC (Wire R/L1 and S/L2)
3G3MV-A4j: 3-phase 380 to 460 VAC
S Makesurethatthemotoroutputterminals(U/T1,V/T2,andW/T3)areconnectedto
the motor correctly.
S Ensure that the control circuit terminals and the control device are wired correctly.
Make sure that all control terminals are turned OFF.
S Set the motor to no-load status (i.e., not connected to the mechanical system).
S Having conducted the above checks, connect the power supply.
4. Check the Display Status
Check to be sure that there are no faults in the Inverter.
S If the display at the time the power is connected is normal, it will read as follows:
RUN indicator: Flashes
ALARM indicator: OFF
Simplified-LED (setting/monitor) indicators: FREF, FOUT, or IOUT is lit.
Data display: Displays the corresponding data of the indicator that is lit.
S When a fault has occurred, the details of the fault will be displayed. In that case,
refer to Chapter 8 Maintenance Operations and take necessary remedies.
5. Initializing Parameters
Initialize the parameters.
S Set n001 to 8 for initialization in 2-wire sequence.
Test Run Chapter 4

Table of Contents

Other manuals for Omron SYSDRIVE 3G3MV

Related product manuals