5-38
· Forn101,set the origin searchdeceleration timeto the timerequired to go from 100%
to 0% of the maximum frequency.
· If 0 is set for the origin search deceleration time, operation will be carried out at the
default setting of 2.0 seconds.
· Forn102,settheoperatinglevelas apercentage, with the Inverter’srated inputtaken
as 100%. If the Inverter’s output current drops below the level of the Inverter’s output
current, the speed search will be completed and acceleration will be resumed.
5-10-2 Multi-function digital Output
The 3G3MV incorporates three multi-functiondigitaloutput terminals: one
multi-functioncontactoutputs(MA-MC)andtwomulti-functionphotocoup-
ler outputs (P1 and P2).
Output from these terminals has a variety of functions according to the
application.
H Selecting the Multi-function digital Output (n050 through n056)
n057 Multi-function digital Output 1
(MA/MB and MC)
Register 0139
Hex
Changes during
operation
No
Setting
range
1 to 7, 10 to 21 (see note) Unit of
setting
1 Default setting 0
n058 Multi-function digital Output 2
(P1 and PC)
Register 013A
Hex
Changes during
operation
No
Setting
range
1 to 7, 10 to 21 (see note) Unit of
setting
1 Default setting 1
n059 Multi-function digital Output 3
(P2 and PC)
Register 013B
Hex
Changes during
operation
No
Setting
range
1 to 7, 10 to 21 (see note) Unit of
setting
1 Default setting 2
Note Set values 20 and 21 are available for 5.5- and 7.5-kW Inverters only.
Set Values
Value Function Description
0 Fault output ON: Fault output (with protective function working)
1 Operation in progress ON: Operation in progress (with RUN command input or
inverter output)
2 Frequency detection ON: Frequency detection (with frequency reference
coinciding with output frequency)
Basic Operation Chapter 5