EasyManua.ls Logo

Omron SYSDRIVE 3G3MV - Communications Response Time

Omron SYSDRIVE 3G3MV
348 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-58
7-9-6 Communications Response Time
The communications response times for communications with an Inverter via the
RS-422/485 port of an OMRON-madeCommunications Board aredetailed below. Use
this information asareference when decidingthe number ofSlaves tobe connected to
one network, and when considering the timing of input and output signals.
H Communications Time for One Message
·A wide variety of programsfor RS-422/485 communications can becreated using the
protocolmacrofunction.Thecommunicationstimeswillvaryaccordingtothecontents
of the program.
·In general, the communications time for one message canbe calculated using the fol-
lowing formula.
Communications time = [No. of bytes in DSR message ´ 10 (see note 1) ´ (1/baud
rate)´ 1,000(ms)]+[No.ofbytesinresponse´ 10´ (1/baudrate)´ 1,000(ms)]+[24
´ (1/baud rate) ´ 1,000 (ms)] + send wait time setting n156 (ms) + protocol macro
waiting time (see note 2) (ms)
Note 1. ThereasonthatthenumberofbytesintheDSRmessageandresponseismul-
tiplied by 10 is because both the start bit and the stop bit require one bit each.
(1 byte = 8 bits) + (start bit: 1 bit) + (stop bit: 1 bit) = 10 bits
Note 2. With RS-422/485 communications, set at least 20 ms as the protocol macro
waiting time.
D Calculation Example
The communications time required for one Slave in theprotocol macro created in 7-9-7
Creating a Project File,canbecalculatedaccordingtothe followingformula.(Baudrate
= 19,200 bps.)
Communications time = [(DSR messagetowritedata (13 bytes) +DSR messageto
read (8 bytes)) ´ 10 ´ (1/19,200) ´ 1,000 (ms)] + [(write response (8 bytes) + read
response(7bytes))´ 10´ (1/19,200)´ 1,000 (ms)]+[24´ (1/19,200) ´ 1,000(ms)´
2] + [10 (ms) ´ 2] + [20 (ms) ´ 2] = 81.2 (ms)
Note If there are N Slaves, the total communications time will be N ´ 81.2 ms. Conse-
quently, the more Slaves that are used, the longer the communications time will
be. If the number of Slaves is too high, it is possible that the detection time of 2 s
for communications time-over will be exceeded. In this case, either disable the
time-over detection function and usea different sequence to detect communica-
tionserrors,orincreasethenumberofMasterstherebydecreasingthenumberof
Slaves per Master.
Communications Chapter 7

Table of Contents

Other manuals for Omron SYSDRIVE 3G3MV

Related product manuals