3-2-3 Parameter Read-prohibit Selection (Prohibiting
Data Written to the EEPROM of the Digital
Operator)
·Tostore the parametersetvalues inthe EEPROM of the Digital Operator,set n177for
parameter read-prohibit selection to 0. A protection error (PrE) will be detected by
attempting to read the parameter setvalues in the Inverter with rEd set. This protects
theparametersetvaluesintheEEPROMfromchange.ThePrEdisplayisturnedOFF
by pressing the Mode Key.
Parame-
ter
Register Name Description Setting
range
Unit of
setting
Default
setting
Chan-
ges dur-
ing
opera-
tion
n177 01B1 Parame-
ter read-
prohibit
selection
Used to keep the data in the
EEPROM of the Digital
Operator on hold.
0: Parameter read-prohibit
(No data can be written to
the EEPROM)
1: Parameter read possible
(Data can be written to the
EEPROM)
0, 1 1 1 No
Note 1. No data can be written to n177 unless the default setting is changed. To write
datatothisparameter,setn001 for parameter write-prohibitselection/parame-
ter initialization to 4.
Note 2. TheparametersettinghasaneffectontheDigitalOperator.IftheDigitalOpera-
torwiththedataintheEEPROMprotectedismountedtoanotherInverter,n117
will be set to 0 regardless of the n117 setting in the Inverter.
D Steps to Set Parameter Read-prohibit
Key
sequence
Indicator Display
example
Explanation
Power ON
Press the Mode Key repeatedly until the
PRGM indicator is lit.
Use the Increment or Decrement Key to
display “n177.”
Press the Enter Key. The present set data will
be displayed.