6-7
Deceleration
The Inverter decelerates normally and is not in energy-saving control.
Power
consumption
Load rate: 100%
Load rate: 50%
Motor voltage
As shown in the graph, the voltage to
operate the motor most efficiently
varies with the motor load condition.
The Inverter in energy-saving control
adjusts the output voltage by using
the ideal calculated value so that the
actual output power will be minimum.
6-2-2 Performing Energy-saving Settings
n139 Energy-saving Control
Selection
Register 018B
Hex
Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 Energy-saving control disabled
1 Energy-saving control enabled
Note 1. Set n139 to 1 to enable energy-saving control.
Note 2. Energy-saving control is enabled within a frequency range from 15 to 120 Hz
and disabled if the frequency exceeds 120 Hz.
n158 Motor Code Register 019E
Hex
Changes during
operation
No
Setting
range
0 to 70 Unit of
setting
1 Default setting See
note
Note The default setting varies with the capacity of the Inverter model.
Set Values
·The motor code is used for automatically setting the energy-saving constant in n140.
·Bysettingthemotorcode, the value in n140(energy-savingcontrolcoefficientK2)will
change automatically. To adjust energy-saving control coefficient K2, set the motor
code in advance.
Advanced Operation Chapter 6