6-47
H Frequency Detection
·Themulti-functionoutputs(n057to n059) must be settothefollowinginorder toissue
an output indicating that the frequency reference and the output frequency agree.
Set value: 2 for frequency agree
Frequency Detection Operation
Output
frequency
Detection width ±2 Hz
Reset width ±4 Hz
Frequency reference
Time
Frequency
detection
Time
H Frequency Detection Levels 1 and 2
·The parameters in n057 to n059 for multi-function output must be set for frequency
detection output.
Set value: 4 for frequency detection level 1 (Output frequency n095)
Set value: 5 for frequency detection level 2 (Output frequency n095)
·Set the frequency detection level in n095.
n095 Frequency Detection Level Register 015F
Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz) Unit of
setting
0.01 Hz Default setting 0.00
Set Values
·Set the frequency to be detected.
Advanced Operation Chapter 6