n082 Number of Fault Retries Register 0152
Hex
Changes during
operation
No
Setting
range
0 to 10 Unit of
setting
1 Default setting 0
Set Values
·Set the number of fault retries required.
·The count of fault retries will be cleared in any of the following cases.
The Inverter is normal for 10 minutes continuously after the latest fault retry was
made.
Power supply to the Inverter is interrupted.
A fault reset is input.
6-10-6 Frequency Jump Function (n083 to n086)
·The frequency jump function prevents the Inverter from generating frequencies that
make the mechanical system resonate.
·The frequency jump function can be used effectively to set three dead bands of a fre-
quency reference.
n083 Jump Frequency 1 Register 0153
Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz) Unit of
setting
0.01 Hz Default setting 0.00
n084 Jump Frequency 2 Register 0154
Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz) Unit of
setting
0.01 Hz Default setting 0.00
n085 Jump Frequency 3 Register 0155
Hex
Changes during
operation
No
Setting
range
0.00 to 400.0 (Hz) Unit of
setting
0.01 Hz Default setting 0.00
n086 Jump Width Register 0156
Hex
Changes during
operation
No
Setting
range
0.00 to 25.50 (Hz) Unit of
setting
0.01 Hz Default setting 0.00
Set Values
·Set n083 through n085 forjumpfrequencies1 through 3 to the central values of jump-
ing frequencies.