5-4 Setting the Local/Remote Mode
The 3G3MV operates in local or remote mode. The following description
provides information on these modes and how to select them.
H Basic Concept
Operation mode Basic concept Description
Local The Inverter in a system
operates independently in
this mode so that the
Inverter can be checked
independently.
Operation Command
Starts with the RUN Key of the Digital
Operator and stops with the
STOP/RESET Key.
Frequency Reference
Set with the Digital Operator or the FREQ
adjuster.
Set with frequency reference selection in
local mode in n007.
Remote The Inverter in a system
operates according to the
control signal of the host
controller.
Operation Command
Selectable from four types and set in
n003.
Frequency Reference
Selectable from ten types and set in
n004.
H Local/Remote Selection Methods
·Thefollowingtwoselectionmethods areavailabletoset theInverterto localorremote
mode. However, it is not possible to switch between local and remote modes during
operation command input.
S Select the mode with the LO/RE Key of the Digital Operator.
S Setanyoneofmulti-functioninputs1through7(n050throughn056)to17tosetthe
Inverter to local mode with control input turned ON.
Note Iftheabovesettingismade,modeselectionwillbe possibleonlywithmulti--func-
tion input, and not with the Digital Operator.
·The inverter always goes into remote mode when the power is turned ON. To operate
immediately afterpower--up, presetthe RUNcommand andfrequency referenceset-
tings in remote mode.