5-41
5-11 Multi-function Analog Output and Pulse Monitor
Output
The 3G3MV Inverter incorporates a multi-function analog output terminal
(AM-AC). A parameter setting makes it possible to output pulse monitor
signals from these terminals. Make the necessary settings in these termi-
nals according to the application.
5-11-1 Setting the Multi-function Analog Output (n065
through n067)
·By setting n065 for multi-function analog output type selection to 0 for analog voltage
output, analog monitoring is possible through the multi-function analog output termi-
nal.
·A monitoring item is set in n066 (multi-function analog output selection). Six items
including the output frequency and current are available.
·Set the analog output characteristics in n067 (multi-function analog output gain).
n065 Multi-function Analog Output
Type Selection
Register 0141
Hex
Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 Analog voltage output (with monitoring item set in n066)
1 Pulse train output (according to output frequency set in n150)
n066 Multi-function Analog Output Register 0142
Hex
Changes during
operation
No
Setting
range
0 to 5 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 Output frequency (Reference: 10-V output at max. frequency)
1 Output current (Reference: 10-V output at rated inverter output current)
2 Main circuit DC voltage (Reference: 10-V output at 400 VDC for 200-V
models and 800 VDC for 400-V models)
3 Vector operation torque monitor (Reference: 10-V output at rated motor
torque)
Basic Operation Chapter 5