6-35
6-7 Overtorque Detection Function
When an excessive load is applied to the equipment, the Inverter detects
the overtorque condition through an increase in the output current.
n096 Overtorque Detection
Function Selection 1
Register 0160
Hex
Changes during
operation
No
Setting
range
0 to 4 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 Inverter does not monitor overtorque.
1 Inverter monitors overtorque only when speed is matched. It continues
operation (issues warning) even after overtorque is detected.
2 Inverter monitors overtorque only when speed is matched. It discontinues
operation (through protective function) when overtorque is detected.
3 Inverter always monitors overtorque during operation. It continues operation
(issues warning) even after overtorque is detected.
4 Inverter always monitors overtorque during operation. It discontinues
operation (through protective function) when overtorque is detected.
·Setn097(overtorquedetectionfunctionselection2),n098(overtorquedetectionlevel)
andn099(overtorquedetectiontime)to enabletheovertorquedetectionfunction.The
Inverter will detect overtorque when the current is the same as or higher than the
detection level is output for the preset detection time.
·Set a multi-function output (n057 to n059) to either of the following so that external
overtorque detection output will be ON.
Set Value: 6 for overtorque detection (NO)
Set Value: 7 for overtorque detection (NC)
Overtorque Detection
Output current
(or output
torque)
n098 (Overtorque
detection level)
Time
Overtorque
detection (NO)
n099
Overtorque detection time
Time
Note Overtorquedetectionwillbecancelediftheoutputcurrentdecreasesfromthedetectionlevelbyapprox-
imately 5% of the Inverter rated current.
See note.
Advanced Operation Chapter 6