6-36
n097 Overtorque Detection
Function Selection 2
Register 0161
Hex
Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 Detects overtorque from output torque.
1 Detects overtorque from output current.
·Set n097 to the item used for overtorque detection.
·In V/f control mode, overtorque is detected through the output current of the Inverter
regardless of the set value.
n098 Overtorque Detection Level Register 0162
Hex
Changes during
operation
No
Setting
range
30 to 200 (%) Unit of
setting
1% Default setting 160
Set Values
·Set n098 to the type of overtorque detection level.
Todetect the levelthrough the output torque,set the torque inpercentage based on
the rated motor torque as 100%.
Todetectthelevelthroughtheoutputcurrent,setthecurrentinpercentagebasedon
the rated current of the Inverter as 100%.
n099 Overtorque Detection Time Register 0163
Hex
Changes during
operation
No
Setting
range
0.1 to 10.0 (s) Unit of
setting
0.1 s Default setting 0.1
Set Values
·Set the overtorque detection time.
·The Inverter will detect overtorquewhen the current (or torque)the same asor higher
than the detection level is output for the preset detection time.
Advanced Operation Chapter 6