EasyManua.ls Logo

Omron SYSDRIVE 3G3MV

Omron SYSDRIVE 3G3MV
348 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-21
Lengthen the acceleration time or reduce the load. Also consider increasing the
motor capacity.
H The motor only rotates in one direction.
·Reverse rotation-prohibit is selected.
If n006 for reverse rotation-prohibit selection is set to 1 (reverse run prohibited), the
Inverter will not accept reverse-rotation commands.
To use both forward and reverse rotation, set n05 to 0.
8-2-3 Motor Rotates in the Wrong Direction
·The output wiring of the motor is faulty.
WhentheU,V,andWterminalsoftheInverterareproperlyconnectedtotheU,Vand
Wterminalsofthemotor,themotorwilloperateinaforwarddirectionwhenaforward
rotation commandis executed.The forwarddirection dependson themanufacturer
and the motor type. Therefore, be sure to check the specifications.
Switching two wires among the U, V, and W will reverse the direction of rotation.
8-2-4 Motor Outputs No Torque or Acceleration is Slow
·The Inverter in vector control is restricted by the torque compensation limit.
If the torque compensation limit in n109 is set to a value that is too small, the motor
torque will be limited to a low value and sufficient torque will not be available.
If no torque restriction is required, set the parameter to a range from 150% (default
setting) to 200%.
·The stall prevention level during running is too low.
Ifthevalueinn093forstallpreventionlevelduringoperationistoolow,thespeedwill
drop before torque output is turned ON.
Check to be sure that the set value is suitable.
·The stall prevention level during acceleration is too low.
Ifthevalueinn094forstallpreventionlevelduringaccelerationistooslow,theaccel-
eration time will be too long.
Check to be sure that the set value is suitable.
·V/f Control Limit
Unlike vector control, the output torque of the Inverter in V/f control is low at low fre-
quencies. Consider the use of vector control if higher output torque at low frequen-
cies is required.
Maintenance Operations Chapter 8

Table of Contents

Other manuals for Omron SYSDRIVE 3G3MV

Related product manuals