5-11
5-5 Selecting the Operation Command
The following description provides information on how to input operation
commandstostartorstoptheInverterorchangethedirectionofrotationof
the Inverter.
Two types of command input methods are available. Select either one of
them according to the application.
H Selecting the Operation Mode (n003)
·Select the method of operation mode input to start or stop the Inverter.
·The following method is enabled in remote mode only. The command can be input
through key sequences on the Digital Operator.
n003 Operation Command
Selection
Register 0103
Hex
Changes during
operation
No
Setting
range
0 to 3 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 The RUN and STOP/RESET Keys of the Digital Operator are enabled.
1 Multi-function input in 2- or 3-wire sequence through the control circuit
terminals is enabled.
2 MODBUS RS-422/485 communications are enabled.
3 Input from optional the CompoBus/D Communications Unit is enabled.
H Selecting the STOP/RESET Key Function (n007)
·When parameter n003 is notsetto0, set whether ornot tousetheSTOP/RESETKey
of the Digital Operator to stop the Inverter in remote mode. The STOP/RESET Key is
always enabled in local mode regardless of the setting in n003.
n007 STOP Key Function Selection Register 0107
Hex
Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 The STOP/RESET Key of the Digital Operator is enabled.
1 The STOP/RESET Key of the Digital Operator is disabled.
Basic Operation Chapter 5