4-8
4 Setting the Motor Current Parameter
·Run the Inverter in V/f control mode for trial operation. The control mode is not initial-
ized.Therefore,setn002to0forV/fcontrol.Setthemotorcurrentparameterinn036in
order to prevent the motor from burning due to overloading.
H Control Mode Setting
Parame-
ter
Register Name Description Setting
range
Unit of
setting
Default
setting
Chan-
ges dur-
ing
opera-
tion
n002 0102 Control
mode
selection
Sets the control mode for the
Inverter.
0: V/f control mode
1: Vector control mode
Note 1. The control mode
is not initialized
with n001 set-
tings.
Note 2. There are param-
eters that are
changed accord-
ing to the set
value in n002. For
details, refer to
5-1-2 Setting the
Control Mode
(n002).
0, 1 1 0 No
Key sequence Indicator Display
example
Explanation
The parameter number is displayed.
Use the Increment or Decrement Key to
display “n002.”
Press the Enter Key to display the set value in
n002.
Use the Increment or Decrement key to set
n002 to 0 unless the value is already set to 0,
during which the display flashes.
Press the Enter Key so that the set value will
be entered and the data display will be lit.
In approximately
1 s.
The parameter number will be displayed again
in approximately 1 s.
Test Run Chapter 4