8-31
H Replacement of Cooling Fan
If the FAN fault is displayed or the cooling fan needs replacement, take the following
steps to replace it.
D Cooling Fan Models
Inverter Cooling Fan
3-phase 200-VAC
3G3MV-A2007 3G3IV-PFAN2007
3
-
p
h
a
s
e
2
0
0
-
V
A
C
3G3MV-A2015 3G3IV-PFAN2015M
3G3MV-A2022 3G3IV-PFAN2022
3G3MV-A2040 3G3IV-PFAN2037
3G3MV-A2055/--A2075 3G3IV-PFAN2037 (2 parts)
Single-phase
2
0
0
-
V
A
C
3G3MV-AB015 3G3IV-PFAN2015M
S
i
n
g
l
e
-
p
h
a
s
e
200-VAC
3G3MV-AB022 3G3IV-PFAN2037
3G3MV-AB040 3G3IV-PFAN2037 (2 parts)
3-phase 400-VAC
3G3MV-A4015/-A4022 3G3IV-PFAN2015M
3
-
p
h
a
s
e
4
0
0
-
V
A
C
3G3MV-A4030/-A4040 3G3IV-PFAN2037
3G3MV-A4055/-A4075 3G3IV-PFAN2037 (2 parts)
D Replacing Cooling Fan of 68-mm-wide Inverter Model
1. Presstheleftandrightsidesofthefancoverlocatedonthelowerpartoftheradiation
fin in the arrow 1directions.Then liftthe bottom of theFan in the arrow 2 directionto
remove the Fan as shown in the following illustration.
Radiation fin (Heat sink)
Wind direction
2. Hold the fan wire and pull the protective tube of the cover in the arrow 3 direction.
Protective tube
There is a connector inside.
Fan wind direction
3. Slide the protective tube and remove the internal connector.
Maintenance Operations Chapter 8