H Conforming to EC Directives
D Wiring the Power Supply
Make sure that the Inverter and Noise Filter are grounded together.
·Alwaysconnectthepowerinputterminals(R/L1,S/L2,andT/L3)andpowersupplyvia
a dedicated Noise Filter.
·Reduce the length of the ground wire as much as possible.
·Locate the Noise Filter as close as possible to the Inverter. Make sure that the cable
length between the Noise Filter and the Inverter does not exceed 40 cm.
·The following Noise Filters are available (all footprint type).
3-phase 200-VAC Noise Filter
Inverter 3-phase 200-VAC Noise Filter
Model 3G3MV- Model 3G3MV- Rated current (A)
A2001/A2002/A2004/A2007 PFI2010-E 10
A2015/A2022 PFI2020-E 16 to 20
A2040 PFI2030-E 26 to 30
A2055/A2075 PFI2050--E 50
Single-phase 200-VAC Noise Filter
Inverter Single-phase 200-VAC Noise Filter
Model 3G3MV- Model 3G3MV- Rated current (A)
AB001/AB002/AB004 PFI1010-E 10
AB007/AB015 PFI1020-E 20
AB022 PFI1030-E 30
AB040 PFI1040-E 40
3-phase 400-VAC Noise Filter
Inverter 3-phase 400-VAC Noise Filter
Model 3G3MV- Model 3G3MV- Rated current (A)
A4002/A4004 PFI3005-E 5
A4007/A4015/A4022 PFI3010-E 10
A4030/A4040 PFI3020-E 15 to 20
A4055/A4075 PFI3030--E 30