5-42
Value Description
4 Output power (Reference: 10-V output at power equivalent to max. applicable
motor capacity and 0-V output during regenerative operation).
5 Output voltage (Reference: 10-V output at 200 VAC for 200-V models and
400 VAC for 400-V models)
Note Output power cannot be monitored in vector control mode
n067 Multi-function Analog Out-
put Gain
Register 0143
Hex
Changes during
operation
Yes
Setting
range
0.00 to 2.00 Unit of
setting
0.01 Default setting 1.00
Note 1. Refer to the above informationonthe setvalues in n066 andset the multiplica-
tion rate based on the reference value. For example, if5-V outputis desiredat
maximum output frequency (with n066 set to 0), set n067 to 0.50.
Note 2. The multi-function analog output terminals(AM and AC)have a maximumout-
put of 10 V.
5-11-2 Setting the Pulse Monitor Output (n065 and n150)
·By setting n065 for multi-function analog output type selection to 1 for pulse train out-
put, monitoring pulse output frequency signals is possible through the multi-function
analog output terminals.
·The relationship between the outputfrequencyandpulse train output frequencyis set
in n150 for multi-function analog output, pulse train frequency selection.
n065 Multi-function Analog Out-
put Type Selection
Register 0141
Hex
Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 Analog voltage output (with monitoring item set in n066)
1 Pulse train output (according to output frequency set in n150)
n150 Multi-function Analog
Output, Pulse Train
Frequency Selection
Register 0197
Hex
Changes during
operation
No
Setting
range
0, 1, 6, 12, 24, and 36 Unit of
setting
1 Default setting 0
Basic Operation Chapter 5