·Valueswillbesetin0.01-Hzincrementsifthefrequencyislessthan100Hzand0.1-Hz
increments if the frequency is 100 Hz or over.
·These values must satisfy the following condition.
n083 n084 n085
·The value in n086 must be set for the jump width.
·This function is disabled with n086 set to 0.0.
·The operation of the Inverter within the dead bands is prohibited. While the Inverter is
in acceleration or deceleration control,however,the Inverter does not jumpthebands
but changes the frequency smoothly.
Frequency Jump Function
Output
frequency
Reference
frequency
6-10-7 Accumulated Operating Time (n087, n088)
· The accumulated operating time function is provided for 5.5- and 7.5-kW Inverters
only.
· This function calculates and stores in memory the Inverter’s accumulated operating
time. The accumulated operating time that is saved can be checked (unit: 10h) by the
“accumulated operating time” (U--13) of the multi-function monitor (MNTR indicator).
· Use this function in determining the maintenance schedule.
n087 Accumulated Operating
Time
Register 0157
Hex
Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0