6-48
·The value will be set in 0.01-Hz increments if the frequency is less than 100 Hz and
0.1-Hz increments if the frequency is 100 Hz or over.
Frequency Detection Level 1
Output
frequency
Reset width --2 Hz
n095 (Frequency
detection level)
Time
Frequency
detection level 1
Time
Frequency Detection Level 2
Output
frequency
Reset width +2 Hz
n095 (Frequency
detection level)
Time
Frequency
detection level 2
Time
6-10-9 UP/DOWN Command Frequency Memory (n100)
·This function changes the reference frequency by turning the UP and DOWN com-
mands ON and OFF.
·In order to use this function, set n056 for multi-function input 7 to 34. Then the multi-
function input 6 (S6) and multi-function input 7 (S7) terminals are set as described
below.
Multi-function input 6 (S6): UP command
Multi-function input 7 (S7): DOWN command
·The output frequency held by the UP/DOWN function will be stored in the memory if
n100 for UP/DOWN frequency storage is set to 1.
·By setting n100 to 1, the frequency reference kept on hold for 5 s or more will be
retained even after a power interruption, and operation will be restarted at this fre-
quency the next time the RUN command is input.
Advanced Operation Chapter 6