·The stored output frequency will be cleared from the memory if n100 is set to 0. The
retained frequency is initialized if n001 for parameter initialization is set to 8 or 9.
Note While this function is used, frequency references can only be used in remote
mode with the UP/DOWN command or inching frequency command. All multi-
step speed references are disabled.
n100 UP/DOWN Frequency
Selection
Register 0164
Hex
Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 The frequency on hold is not retained.
1 The frequency on hold for 5 s or more is retained.
Operation of UP/DOWN Function
RUN command
(Forward rotation)
UP command
(S5)
DOWN command
(S6)
Output frequency
Upper limit
Lower limit
Status
Frequency
detection
Time
Note Status U: UP (acceleration)
D: DOWN (deceleration)
H: Hold
U1: Frequency acceleration restricted by upper limit.
D1: Frequency deceleration restricted by lower limit.
Time
Time
Time
Time