4-9
H Setting the Rated Motor Current
Parame-
ter
Register Name Description Setting
range
Unit of
setting
Default
setting
Chan-
ges dur-
ing
opera-
tion
n036 0124 Rated
motor
current
Used to set the rated motor
current (A) used for the ref-
erence current of motor
overload detection (OL1).
Note 1. The default set-
ting for the rated
motor current is
the standard rated
current of the
maximum applica-
ble motor.
Note 2. Motor overload
detection (OL1) is
disabled by set-
ting the parameter
to 0.0.
0.0% to
150%
(A) of
rated
output
current
of the
Inverter
0.1 A See note
1 under
Descrip-
tion.”)
No
Key sequence Indicator Display
example
Explanation
The parameter number is displayed.
Use the Increment or Decrement Key to
display n036.
Press the Enter Key to display the set value in
n036.
Use the Increment or Decrement Key to set
n036 to the rated motor current, during which
the display flashes.
Press the Enter Key so that the set value will
be entered and the data display will be lit.
In approximately
1 s.
The parameter number will be displayed again
in approximately 1 s.