6-34
·If n115 is set to 1,the stall prevention level willbe suppressed asshown below. When
using frequencies exceeding the maximum voltage frequency, set n 115 to 1.
Operation level
Automatic Suppression of Stall Prevention Level (n115 Set to 1)
Constant output range
Operating level: n094 x
(Max. voltage
frequency/output frequency)
Max. voltage frequency (FA)
Output frequency
40% of n094
n116 Stall Prevention
Acceleration/Deceleration
Time Setting
Register 0174
Hex
Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Set Values 0
Set Values
Value Description
0 Accelerates or decelerates at acceleration/deceleration time 1 or 2 presently
selected.
1 Accelerates or decelerates at acceleration/deceleration time 2 set in n021
and n022.
·Select the acceleration/deceleration time with the stall prevention function operating
function enabled.
·Toaccelerateordeceleratequickerorslowerthan normal,set1inn116andtheaccel-
eration time in n021 (acceleration time 2) and deceleration time in n022 (deceleration
time 2) for stall prevention use.
Advanced Operation Chapter 6