5-39
Value DescriptionFunction
3 Zero-speed ON: Idling (at less than min. output frequency)
4 Frequency detection 1 ON: Output frequency frequency detection level
(n095)
5 Frequency detection 2 ON: Output frequency frequency detection level
(n095)
6 Overtorque being
monitored
(NO-contact output)
Output if any of the following parameter conditions is
satisfied.
· Overtorque detection function selection 1 (n096)
· Overtorque detection function selection 2 (n097)
7 Overtorque being
monitored
(NC-contact output)
· Overtorque detection level (n098)
· Overtorque detection time (n099)
Note NO contact: ON with overtorque being detected;
NC contact: OFF with overtorque being detected
8 Undertorque detection
(NO)
Closed if undertorque is detected
9 Undertorque detection
(NC)
Open if undertorque is detected
10 Alarm output ON: Alarm being detected (Nonfatal error being
detected)
11 Base block in
progress
ON: Base block in progress (in operation with power
output turned OFF)
12 RUN mode ON: Local mode (with the Digital Operator)
13 Inverter ready ON: Inverter ready to operate (with no fault detected)
14 Fault retry ON: Fault retry (Inverter resetting with fault retry (n082)
not set to 0)
15 UV in progress ON: Undervoltage being monitored (main circuit
undervoltage UV1 detected)
16 Rotating in reverse
direction
ON: Rotating in reverse direction
17 Speed search in
progress
ON: Speed search in progress
18 Communications
output
ON: Communications output (turns ON/OFF according
to 0009 Hex set from communications. Communications
setting = ON)
19 PID feedback loss ON: PID feedback being lost (set detection method in
n136, n137, n138)
20 Frequency reference
is missing
Closed if frequency reference is missing.
21 Inverter overheating
pre-alarm OH3
Closed if inverter overheating pre-alarm is input. Digital
operator display is “OH3” (blinking)
Basic Operation Chapter 5