5-8
n012 Maximum Voltage (VMAX) Register 010C
Hex
Changes during
operation
No
Setting
range
0.1 to 255.0 [0.1 to 510.0] (V) Unit of
setting
0.1 V Default setting 200.0
[400.0]
n013 Maximum Voltage Frequency
(FA)
Register 010D
Hex
Changes during
operation
No
Setting
range
0.2 to 400.0 (Hz) Unit of
setting
0.1
Hz
Default setting 60.0
n014 Middle Output Frequency (FB) Register 010E
Hex
Changes during
operation
No
Setting
range
0.1 to 399.9 (Hz) Unit of
setting
0.1
Hz
Default setting 1.5
n015 Middle Output Frequency
Voltage (VC)
Register 010F
Hex
Changes during
operation
No
Setting
range
0.1 to 255.0 [0.1 to 510.0] (V) Unit of
setting
0.1 V Default setting 12.0
[24.0]
(seenote2)
n016 Minimum Output Frequency
(FMIN)
Register 0110
Hex
Changes during
operation
No
Setting
range
0.1 to 10.0 (Hz) Unit of
setting
0.1
Hz
Default setting 1.5
n017 Minimum Output Frequency
Voltage (VMIN)
Register 0111
Hex
Changes during
operation
No
Setting
range
0.1 to 50.0 [0.1 to 100.0] (V) Unit of
setting
0.1 V Default setting 12.0
[24.0]
(seenote2)
Note 1. [ ] values indicate those for 400-V-class Inverters.
Note 2.For5.5-and7.5-kWInverters,thisvalueissetto10.0Vfor200-V-classmodels
and to 20.0 V for 400-V-class models.
Output
voltage (V)
Note 1. Set the parameters so that
the following condition willbe
satisfied.
n016 n014 < n013 n011
Note 2. The value set in n015 will be
ignored if parameters n016
and n014 are the same in
value.
Frequency (Hz)
n012 (VMAX)
n015 (VC)
n017 (VMIN)
n016
(FMIN)
n014
(FB)
n013
(FA)
n011
(FMAX)
Basic Operation Chapter 5