5-24
·When the frequency reference is changed while the FREF indicator is lit, the corre-
spondingparameterischangedsimultaneously.Forexample,iffrequencyreference2
has been selected with multi-function input (a multi-step speed reference), the set
valueinn025(forfrequencyreference2)willbechangedsimultaneouslywhenthefre-
quency reference is changed while the FREF indicator is lit.
·Take the following default steps, for example, to change the frequency referencewith
the FREF indicator lit.
Key
sequence
Indicator Display
example
Explanation
Power On
Note If the FREF indicatorhas notbeen lit, pressthe
Mode Key repeatedly until the FREF indicator
is lit.
Use the Increment or Decrement Key to set the
frequency reference.
The data display will flash while the frequency
reference is set.
Press the Enter Key so that the set value will be
entered and the data display will be lit.
D Setting the Key Sequential Frequency (n009)
·The Enter Key need not be pressed when changing the setting in n009. In that case,
thefrequencyreferencewillchange whentheset valueischangedwith theIncrement
or Decrement Key while the data display is continuously lit.
n009 Key Sequential Frequency
Setting
Regis-
ter
0109
Hex
Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 Enter Key enabled (The set value is entered with the Enter Key pressed.)
1 Enter Key disabled (The set value set is entered immediately.)
Basic Operation Chapter 5