6-12
·Set the width in percentage based on the power to be detected as 100%.
·Normally, the default setting does not need to be changed.
·The Inverter will operate with a power detection width of 10% if the value is set to 0.
n162 Power Detection Filter
Constant
Register 01A2
Hex
Changes during
operation
No
Setting
range
0 to 255 Unit of
setting
1 (4 ms) Default setting 5
Set Values
·SetthisparametertothefiltertimeconstantofthepowerdetectionblockoftheInverter
operating in probe operation.
Filter time constant (ms) = Set value in n162 x 4 (ms)
·Normally, the default setting does not need to be changed.
·The Inverter will operate with a time constant of 20 ms if the value is set to 0.
Advanced Operation Chapter 6