6-28
Voltage Set to 4
Reduced
rated output
current (A)
Set to 3
Reduced
rated output
current (A)
Rated
output
current (A)
Default
setting
Model
3G3MV-
Single-phase
2
0
0
V
AB001 4 (10 kHz) 0.8 ¬ ¬
S
i
n
g
l
e
-
p
h
a
s
e
200 V
AB002 4 (10 kHz) 1.6 ¬ ¬
AB004 4 (10 kHz) 3.0 ¬ ¬
AB007 4 (10 kHz) 5.0 ¬ ¬
AB015 3 (7.5 kHz) 8.0 ¬ 7.0
AB022 3 (7.5 kHz) 11.0 ¬ 10.0
AB040 3 (7.5 kHz) 17.5 ¬ 16.5
3-phase
4
0
0
V
A4002 3 (7.5 kHz) 1.2 ¬ 1.0
3
-
p
h
a
s
e
400 V
A4004 3 (7.5 kHz) 1.8 ¬ 1.6
A4007 3 (7.5 kHz) 3.4 ¬ 3.0
A4015 3 (7.5 kHz) 4.8 ¬ 4.0
A4022 3 (7.5 kHz) 5.5 ¬ 4.8
A4030 3 (7.5 kHz) 7.2 ¬ 6.3
A4040 3 (7.5 kHz) 9.2 ¬ 8.1
A4055 3 (7.5 kHz) 14.8 ¬ ¬
A4075 3 (7.5 kHz) 18 ¬ 17
n175 Low Carrier Frequency at
Low Speed
Register 01AF
Hex
Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Note For 5.5- and 7.5-kW Inverters, the default setting is 1 (enable).
Set Values
Value Description
0 Low carrier frequency at low speed disabled.
1 Low carrier frequency at low speed enabled.
·Normally set n175 to 0 (except for 5.5 and 7.5kW Inverters).
·Whentheoutputfrequencyis5Hzorless andtheoutputcurrentrate is110%ormore,
the carrier frequency will be automaticallyreduced to 2.5 kHzwith n175 setto1. If the
load is heavy at low speed, the Inverter will withstand higher overcurrent by suppres-
sing the heat radiation of the Inverter caused by the carrier frequency.
·This function is enabled with 2, 3, or 4 set in n080 for carrier frequency.
Advanced Operation Chapter 6