6-32
n093 Stall Prevention Level
during Acceleration
Register 015D
Hex
Changes during
operation
No
Setting
range
30 to 200 (%) Unit of
setting
1% Set Values 170
Set Values
·Thisfunctionisused to stop accelerating the loadiftheoutputcurrentexceeds theset
current value so that the Inverter will continue operating without stalling. The Inverter
accelerates the load while theoutputcurrentis the same asor less thanthe set value.
·Set the parameter as percentage based on the rated Inverter current as 100%.
·The default setting does not need any changes in normal operation.
·DecreasethesetvalueifthecapacityofthemotorissmallerthanthatoftheInverteror
the motor stalls with the default value.
Thesetvalueisnormally2or3timeshigherthantheratedcurrentofthemotor.Setthis
current as percentage based on the rated inverter current as 100%.
Stall Prevention during Acceleration
Output
current
n093 (stall prevention level
during acceleration)
Time
Output
frequency
The output frequency is controlled
so that the Inverter will not stall.
Time
n094 Stall Prevention Level
during Operation
Register 015E
Hex
Changes during
operation
No
Setting
range
30 to 200 (%) Unit of
setting
1% Default setting 160
Set Values
·This function will decrease the output frequency if the output current exceeds the set
current value byaminimum of approximately100 ms sothat theInverter will continue
operating without stalling. The Inverter will increase the output frequency to return to
the set frequency reference level when the output current is less than the set value.
Advanced Operation Chapter 6